Connexion RET & REF Series Direct Acting
Stainless 316 Pressure Reducing Valve
 

  Connexion BSP Range of 316 Stainlesss Steel Valve Body is suitable for Fluid, Air, Liquid and Steam.

 The valve is specially designed to operate in an open condition  which will not be influenced by the water supply function under unstable inlet pressure condition. When the outlet pressure responds directly to the pressure control chamber and adjusts the setting pressure, it responds quickly and adjusts the pressure accurately.

 Special piston and diaphragm design improves the ability of sustaining pressure and reducing leakage.
 
Pressure Adjusting Range :
1 to 6 Bar 
4 to 10 Bar 
8 to 13 Bar (other options upon request)

Pressure needed from fully-closed gate to full-opened gate :1.5 Bar (1 Bar = 14.5 psi)
Applied Temperature : -15C to +100C or -15C to +200C (For Steam)
 
 
 
 
Sizes 1/2 to 2" BSP / NPT or DN15 to DN150 mm PN16 Flange
   
RET Series Direct Acting Pressure reducing Valves from Connexion
No
Part Name
Material
1
Gauage
Upon request
2
Cover
316 Stainless Steel
3
O-ring
Viton
4
Piston
316 Stainless Steel
5
Sealing spacer
Viton
6
Shaft
316 Stainless Steel
7
Main body
316 Stainless Steel
8
Diaphragm
Viton
9
O-ring
Viton
10
Spring
Spring Steel
11
Spring cover
316 Stainless Steel
12
Washer
Brass
13
Adjusting stem
316 Stainless Steel
 
 
 
 
 
 
 
 
  
Item NoSizeH(mm)L(mm)CV
RET15-S1/2"80702.4
RET20-S3/4"105859.0
RET25-S1"1059211.0
RET40-S1 1/2"13011521.0
RET50-S2"13012025.0
 Applied condition of Direct-activated Pressure Reducing Valve:
 
    Installing pressure reducing valve directly in sub-pipe can reduce fluid pressure inside the pipe.
    Installing a filter in the inlet of pressure reducing valve can prevent block of valve gate caused by impurities and limescale.
    Installing pressure relief valve downstream pressure reducing vale can protect the system.
   While using screws to connect pressure reducing valve, joints should be installed in the inlet and outlet to make maintenance easy.
 

 Pressure Setting and Flow Rate of Direct-activated Pressure Reducing Valve:
 
Direct-activated pressure reducing valve directly opens and closed the valve gate by the outlet pressure. When outlet pressure is under setting pressure, valve gate automatically opens. To make valve gate fully open, adjustable pressure range and setting pressure are relative points.

A : Pressure drop needed for fully-opened valve gate = B/4 , B-Adjustable Pressure Range Maximum-Minimum

B : Adjustable Pressure Range (-Maximum Minimum Adjustable Pressure Range)

C : Setting Pressure of Outlet

P : Pressure of fully-opened outlet valve gate, P-C-A

Example:
Pressure drop need for fully-opened valve gate for adjusting pressure range 3~9 kgf/cm2 of direct-activated pressure reducing valve.
If the setting pressure of outlet is 6 kgf/cm2, pressure of fully-opened valve gate will be P=6-1.5=4.5 kgf/cm2

 
 
 REF 316 stainless steel direct ating pressure reducing valves
 
REF Flanged series direct acting pressure reduciing valve
 
 
 
 
No
Part Name
Material
1
Gauage
Upon request
2
Cover
316 Stainless Steel
3
O-ring
Viton
4
Piston
316 Stainless Steel
5
Sealing spacer
Viton
6
Shaft
316 Stainless Steel
7
Main body
316 Stainless Steel
8
Diaphragm
Viton
9
O-ring
Viton
10
Spring
Spring Steel
11
Spring cover
316 Stainless Steel
12
Washer
Brass
13
Adjusting stem
316 Stainless Steel